1SM6LE-63 leakage circuit breaker is a circuit breaker to install leakage protector for AC 50Hz, rated voltage single-phase 230V, three-phase 400V and below, rated current 1 ~ 63A circuit, leakage short-circuit and overload fault Reliable protection. 30mA action current can be used for indirect contact electric shock and insulation failure protection and direct contact with the supplementary protection.
Technical Parameters
Rated current: 1,3,6,10,16,20,25,32,40,50, 63A
Rated voltage: 230 / 400V
Number of poles: 1P + N, 2P, 3P, 3P + N, 4P
Rated leakage current: 30mA
Rated leakage non-operating current: 15mA
Breaking time: <0.1s
Breaking capacity: 4500A
Tripping characteristics:
C curve:
D-shaped curve:
Mechanical and electrical life: 4000 times (off a pass)
Products meet GB16917.1, IEC61009-1 standard
Wiring: When the following 40A and 40A, with clamps of the terminals, apply In 16mm2 and below the hard wire
Wiring: When more than 50A, using the clamp with the terminals, suitable for 25mm2 and below the hard wire
Installation: Standard type TH35-7.5 installation rail.
Application Guide
Leakage trip indicators in the front of the device.
Press the test button once a month to check the operation of the leakage protection device.
When the leakage protection device is activated, the front of the device has a mechanical indication.
When reclosing the circuit breaker, press the black button, the leakage protection device automatically reset
Installation dimensions and dimensions: In=(1~40A)
Nomber of poles | 1P+N | 2P | 3P | 3P+N | 4P |
A | 45 | 63 | 91 | 99 | 117 |
Installation dimensions and dimensions: In=(50~63A)
Nomber of poles | 1P+N | 2P | 3P | 3P+N | 4P |
A | 54 | 72 | 104 | 117 | 135 |